EAS Constructs OSUs Expansion
EAS was recently contracted to construct, deliver and install (13) large scale custom air handling units for the OSU’s medical center’s new expansion, “Project One”. This build took place at The Ohio State University’s James Cancer Hospital and Solove Research Institute in Columbus, OH. Two different Air Handling Units were used in the off-site construction of the James Cancer Hospital: Double Decker & Triple Decker. As The Ohio State University states, “As the patient-care component of Ohio State’s cancer program, the James Cancer Hospital and Solove Research Institute is a transformational facility that integrates scientific research, education and innovative patient care. Research and education spaces are located on every inpatient floor, enhancing our bench-to-bedside approach to patient care and giving patients early access to new-targeted treatments and tools.” We are glad that EAS and Air Control Products could take part in such a great build.
Project Highlights:
- Total 2,054,000 CFM AHU System, Triple Decker
-
Overall Dimension:First Level: 51′-2″L x 19′-0″W x 12′-7″HSecond Level: 51′-2″L x 19′-0″W x 12′-7″HThird Level: 12′-2″L x 10′-0″W x 12′-7″H
- The AHU was constructed in (12) sections, (5) first level (5) second level (2) third level
- All sections were shipped, unloaded and rigged into place under EAS supervision
- The first level contains: Mixed Air Section, Air Blending, Pre-filter, Intermediate Filter, Carbon Filter, Pre-heat Coils, Cooling Coils, Sound Attenuation, (4) Supply Fans, HEPA Filters, Humidifiers and Supply Smoke Dampers
- The second level contains: Mixed Air Section, Air Blending, Pre-filter, Intermediate Filter, Carbon Filter, Pre-heat Coils, Sound Attenuation, (4) Supply Fans, HEPA Filters, humidifiers and Supply Smoke Dampers
- The third level contains: Intake Smoke Dampers, (4) Return Fans, Supply and Relief Dampers
Technical Details
- Eight (8) 13,750 CFM, 25 HP, 30″ Class II Supply Fans
- Four (4) 17,500 CFM, 30 HP, 30″ Class II Return Fans
- Sound Attenuators for the Supply Fan Inlets
- Two Humidifiers, Dri-Steem Ultra-sorb, 792 lbs. / hr
- Mixing, Return and Relief Dampers, Tamco Series 1500
- Intake and Supply Smoke Dampers, Greenheck HSD-401
- Twelve (12) Cooling Coils, 5/8″ Copper Tubes, .0095″ Aluminum Fins, 16ga 304SS Casing, 4,712 MBH Total Capacity
- Four (4) Pre-heating Coils, 5/8″ Copper Tubes, .0095″ Aluminum Fins, 16ga Galvanized Casing, 2,016 MBH Total Capacity
- Cooling Coils have 16 ga 304 Stainless Steel intermediate Drain pans with Schedule 40 304 Stainless Steel Downspouts
- Intermediate Filters: American Air Filter, 12″ V-Type Filter, MERV 11
- Carbon Filters: Future
- HEPA Filters: American Air Filter, 12” Gasket Seal HEPA, MERV 17
- All Filter Frames are 304 Stainless Steel
- Lighting using T8 Fluorescent 4-foot twin lamp fixtures with electronic dual voltage (120/277V) ballast
- Two (2) inch foam core panel system (R-value of 15.2) with extruded no-through metal framing. Aluminum, 0.050” smooth interior finish and .040” textured aluminum exterior finish and no-through metal framing
- C6 x 11.8 structural steel base for lower level and C6 x 8.2 structural steel for upper level
- Both bases with 2” of foam insulation (R-value 15.2)
- Full sized access doors with 12 x 12 double pain viewing windows
- 3/16” aluminum checkered plate flooring throughout air handing units
- Floor Drains are 8” x 10” x 4” smooth aluminum with removable covers, each drain has all welded schedule 40 aluminum